Starting and stopping methods
(factory set to COAST position)
To coast the motor to a stop
Insure that JMP506 is set to the COAST position as shown
in Figure 13 (page 27). Refer to Figure 4 (page 4) for
Jumper Locations. To coast the motor to a stop open the
ENABLE/DISABLE switch, or remove the jumper between
ENABLE (E2) and COMMON (E1) terminals of TB501.
Refer to (page 19) for instructions on switch installation.
To brake the motor to a stop
Insure that JMP506 is set to the BRAKE position as shown
in Figure 13 (page 27). Refer to Figure 4 (page 4) for
Jumper Locations. Confirm BRAKE CURRENT and
BRAKE TIME potentiometers are calibrated to a desired
value. BREAK CURRENT is adjustable from 0-100% of
rated output current. BRAKE TIME is adjustable from 1 -12
seconds. To brake the motor,